The following are the PDUs that Exadata currently supports or has supported in the
past:
Table 1-24 (page 1-35) Low-voltage 15 kVA Single Phase PDUs for North
America, South America, Japan and Taiwan (2 PDUs per Rack)
Table 1-25 (page 1-36) Low-voltage 15 kVA Three Phase PDUs for North
America, South America, Japan and Taiwan (2 PDUs per Rack)
Table 1-26 (page 1-37) High-voltage 15 kVA Single Phase PDUs for Europe, the
Middle East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and
Taiwan (2 PDUs per Rack)
Table 1-27 (page 1-38) High-voltage 15 kVA Three Phase for Europe, the Middle
East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and Taiwan (2
PDUs per Rack)
Table 1-28 (page 1-39) Low-voltage 22 kVA Single Phase PDUs for North
America, South America, Japan and Taiwan (2 PDUs per Rack)
Table 1-29 (page 1-39) High-voltage 22 kVA Single Phase PDUs for Europe, the
Middle East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and
Taiwan (2 PDUs per Rack)
Table 1-30 (page 1-40) Low-voltage 24 kVA Three Phase PDUs for North
America, South America, Japan and Taiwan (2 PDUs per Rack)
Table 1-31 (page 1-41) High-voltage 24 kVA Three Phase PDUs for Europe, the
Middle East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and
Taiwan (2 PDUs per Rack)
Table 1-32 (page 1-42) Low-voltage 37 kVA Three Phase PDUs for North
America, South America, Japan and Taiwan (2 PDUs per Rack)
Table 1-33 (page 1-42) High-voltage 37 kVA Three Phase PDUs for Europe, the
Middle East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and
Taiwan (2 PDUs per Rack)
Table 1-24 (page 1-35) lists the requirements for low-voltage single-phase PDUs for
North America, South America, Japan, and Taiwan. There are two PDUs per rack. The
following specifications are per PDU.
Table 1-24 Low-voltage 15 kVA Single Phase PDUs for North America, South
America, Japan and Taiwan (2 PDUs per Rack)
Option Requirement, per PDU
Voltage 200 - 240 VAC
Frequency 50/60 Hz
Current 24 A maximum per input
Power rating 15 kVA
Output current 72 A (3 x 24 A)
Outlets 42 x C13; 6 x C19
Outlet groups 6
Group protection (UL489 2-pole circuit
breaker)
20A
Chapter 1
Electrical Power Requirements
1-35