Environmental Requirements
Confirming Specifications 19
Description Value
Idle input power 678 W
Peak AC input power (running SpecJBB) 1480 W
Note - The maximum operating input current values are based on the formula P / (V *0.90),
where P = maximum operating input power and V = input voltage. For example: 620W / (100V
* 0.90) = 6.89A You can use this formula to calculate the maximum operating current at your
input voltage.
Caution - Use only the power cords provided with the server.
Related Information
“Powering On the Server for the First Time”
“Physical Specifications” on page 17
“Environmental Requirements” on page 19
“Airflow Precautions” on page 20
Environmental Requirements
This topic includes these specifications:
Temperature, humidity, and elevation
Shock and vibration
Acoustic
TABLE 1
Temperature, Humidity, and Elevation Specifications
Operating Nonoperating
Description U.S. Metric U.S. Metric Notes
Temperature
(maximum)
41 to 95??F at 0
to 3000 ft
5 to 35??C
at 900m
-40 to 149??F
at 0 to 3000 ft
-40 to 65??C
at 900m
Decrease in maximum temperature:
above 3000 ft. (900m), 1.8°F/1000 ft (1°
C/300m)
Relative
humidity
10 to 90%
at 81??F
10 to 90%
at 27??C
Up to 93%
at 100??F
Up to 93%
at 38??C
Maximum wet bulb, noncondensing
Altitude 0 to 9840 ft at
95°F
0 to 3000m
at 40??C
Up to 40,000 ft Up to 12,000m
Except in China markets where regulations may limit installations to a maximum altitude of 2km.