Airflow Precautions
Confirming Specifications 21
■
Adhere to the minimum airflow clearance specifications. See “Physical
Specifications” on page 17.
■
Install the server so the front faces the cool aisle and the rear faces the warm aisle.
■
Do not direct warm air into the server.
■
Prevent recirculation of air within a rack or cabinet.
■
When servicing server internal components, ensure that air ducts and baffles are properly
installed.
■
Route cables so they do not interfere with airflow.