Optional Controller
Remote Controller Functions
1
5. Detailed Settings Function
Item code Item
Setting data
No. Description
Forced thermostat ON time
0000 5 minutes
0001 4 minutes
Cooling discharge
temperature shift
–010 Shifts discharge temperature setting 10°C down
–009 Shifts discharge temperature setting 9°C down
–008 Shifts discharge temperature setting 8°C down
0010 Shifts discharge temperature setting 10°C up
Heating discharge
temperature shift
–010 Shifts discharge temperature setting 10°C down
–009 Shifts discharge temperature setting 9°C down
–008 Shifts discharge temperature setting 8°C down
0010 Shifts discharge temperature setting 10°C up
Temperature shift for
cooling/heating change in
auto heat/cool mode
0001 ±1°C
0002 ±2°C
0003 ±3°C
0007 ±7°C
(Upper limit)
Change to remote
control temperature
setting range
Cooling
0018 18°C (Lower limit at shipment)
0019 19°C
(Lower limit)
0029 29°C
0030 30°C (Upper limit at shipment)
(Upper limit)
Heating
0016 16°C (Lower limit at shipment)
0017 17°C
(Lower limit)
0029 29°C
0030 30°C (Upper limit at shipment)
(Upper limit)
Drying
0018 18°C (Lower limit at shipment)
0019 19°C
(Lower limit)
0029 29°C
0030 30°C (Upper limit at shipment)
(Upper limit)
Auto heat/cool
0017 17°C (Lower limit at shipment)
0018 18°C
(Lower limit)
0026 26°C
0027 27°C (Upper limit at shipment)
Humidier operation
0000 Normal
0001 Ignore heat exchanger temperature conditions.
Filter (CN70) input
switching
0000 Filter input (differential pressure switch input)
0001 Alarm input (for trouble input about air cleaner or similar device)
0002
Humidier input (Operates linked with drain pump when humidier is
ON.)
Indoor unit electronic
control valve
0000 Present (Setting at shipment)
0002 None
T10 terminal switching
0000 Normal (Used as optional relay PCB or JEMA standard HA terminal.)
0001 Used for OFF reminder
0002 Fire prevention input
SM830241-00_2WAY SYS.indb 10 15/04/07 10:00:31

Table of Contents

Other manuals for Panasonic CZ-RTC4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CZ-RTC4 and is the answer not in the manual?

Panasonic CZ-RTC4 Specifications

General IconGeneral
BrandPanasonic
ModelCZ-RTC4
CategoryRemote Control
LanguageEnglish

Related product manuals