1 - 11
Optional Controller 
Remote Controller Functions
1
5. Detailed Settings Function
Item code Item
Setting data
No. Description
Automatic drain pump 
operation
0000 No forced operation
0001 Forced operation for 1 minute
0060 Continuous operation
Ventilation fan operation
0000 None
0001 Ventilation fan operated by remote controller.
Wired remote controller 
sensor
0000 Not used. (Body sensor is used.)
0001 Remote control sensor is used.
“Operation change 
control in progress” 
display
0000 Normal (displayed)
0001 Not displayed
OFF reminder function 
for when weekly timer is 
used
0000 None
0001 Only stop time setting is enabled.
Discharge temperature 
control
0000 Discharge temperature control OFF
0001 Discharge temperature control ON
Heat exchanger 
temperature for cold air 
discharge  
(Heat exchanger control 
point for control to 
prevent cold air)
0013 Control temperature 13°C
0014 Control temperature 14°C
0025 Control temperature 25°C
0026 Control temperature 26°C
Fan output switching
0000 Output linked with fan. (ON when indoor unit fan is operating.)
0001 Fan mode operation output
Drain pump delayed 
start time
0000 No delayed start
0001 1 second delayed start
Except 
Indoor unit 
 
Type 
U1, F2, 
T1, E1
1 minute delayed start
Indoor unit 
 
Type 
U1, F2, 
T1, E1
0002 2 seconds delayed start 2 minutes delayed start
0058 58 seconds delayed start 58 minutes delayed start
0059 59 seconds delayed start 59 minutes delayed start
0060 60 seconds delayed start 60 minutes delayed start
Humidier setting
0000 Humidier output OFF. Drain pump stopped.
0001 Humidier output ON. Drain pump operates.
0002
Humidier output ON. Drain pump operates for 1 minute when total humidier 
operating time reaches 60 minutes.
0003 Humidier output ON. Drain pump stopped.
Flap operation mode
0000 Standard setting
0001 Draft reduction mode (Flap lower-limit position is shifted upwards.)
Flap swing mode
0000 Smudging reduction mode (Flap swing upper-limit position is shifted downwards.)
0001 Normal mode
0002 Draft reduction mode (Flap swing lower-limit position is upwards.) 
SM830241-00_2WAY SYS.indb   11 15/04/07   10:00:31