FP3 MEWNET-TR
Chapter7-2. Page.98
94
LED status Steps to take
x
When the slave station number is overlapped or the wrong I/O points are set
<Master station ERROR: ON, COM.: OFF, ALARM: Flashing,
Slave stations 1 and 2 COM.: OFF, Other LEDs: normal status>
POWER COM. ALARM
Slave station 1 Slave station 2
POWER COM. ALARM
Master station
RUN
PROG.
TEST
BREAK
ERROR
BATT.
ALARM
COM.
ALARM
<FP3/FP10S
CPU>
<FP3
transmitter
master unit>
S
Check that all slave
station numbers are
correctly registered.
S
Set the I/O points
correctly using
operation mode
selector Nos. 5 through
8.
x
When the ALARM LED on the FP3 transmitter master unit is ON
<Master station ERROR: ON, COM.: OFF, ALARM: ON, Slave stations 1 and
2 COM: OFF, Other LEDs: normal status>
POWER COM. ALARM
Slave station 1 Slave station 2
POWER COM. ALARM
There is probably
an abnormality.
Master station
RUN
PROG.
TEST
BREAK
ERROR
BATT.
ALARM
COM.
ALARM
<FP3/FP10S
CPU>
<FP3
transmitter
master unit>
S
See troubleshooting on
page 98.
7-2. Remote I/O Control When an Error Occurs