FP3 MEWNET-TR
Chapter8-3. Page.124
120
8-3. Settings
1. Operation Mode Selector
1) FP3 transmitter master unit
Selector
Selector position
number
unct
on
escr
p
on
1 2 3 4 5 6 7 8
1
System
configuration
Remote I/O control disabled,
master B of I/O link
ON
selection
Remote I/O control enabled,
master A of I/O link
OFF
2
Output operation
condition during a
Hold (continues I/O control
operation)
ON
communication error
Output OFF OFF
3 and 4
Not used - -
5 and 6
Input points
0 point
OFF OFF
selection of slave
32 points
ON OFF
s
a
on
64 points
OFF ON
128 points
ON ON
7 and 8
Output points
0 point
OFF OFF
selection of slave
32 points
ON OFF
s
a
on
64 points
OFF ON
128 points
ON ON
Notes:
x
The operation mode selectors are all set to the OFF position when shipped.
x
The operation mode selector’s right side is “OFF ( )” and the left side is “ON ( ).”
x
Be sure the power is OFF when changing the selector position.
8-3. Settings
OFFON
1
2
3
4
5
6
7
8
Operation mode selector