FP3 MEWNET-TR
Chapter4-1. Page.55
51
x
Selector numbers 3 and 4:
Not used
x
Selector numbers 5 to 8:
I/O point selection
The I/O points to be used by slave stations are selected by operation mode selector
numbers 5 through 8.
See page 57, ā4-2. I/O Allocation,ā for details about I/O allocation setting and
allocation patterns.
I/O points
Selector number
Input Output
oca
on pa
ern num
er
5 6 7 8
128 128
Pattern No. 1 ON ON ON ON
128 64
Pattern No. 2 ON ON OFF ON
128 32
Pattern No. 3 ON ON ON OFF
128 0
Pattern No. 4 ON ON OFF OFF
64 128
Pattern No. 5 OFF ON ON ON
64 64
Pattern No. 6 OFF ON OFF ON
64 32
Pattern No. 7 OFF ON ON OFF
64 0
Pattern No. 8 OFF ON OFF OFF
32 128
Pattern No. 9 ON OFF ON ON
32 64
Pattern No. 10 ON OFF OFF ON
32 32
Pattern No. 11 ON OFF ON OFF
32 0
Pattern No. 12 ON OFF OFF OFF
0 128
Pattern No. 13 OFF OFF ON ON
0 64
Pattern No. 14 OFF OFF OFF ON
0 32
Pattern No. 15 OFF OFF ON OFF
Note:
x
Since the FP3 transmitter master unit has no selector for terminal station setting, it must be located on the
network as a terminal.
2) Operation mode when shipped
x The operation mode selector numbers are all set to the OFF position when shipped.
x Operation mode setting when shipped:
- The unit is used as a MEWNET-TR master station.
- When an abnormality occurs during operation, all slave stations stop I/O control.
- The I/O points used are as follows:
Input: 0 point, Output: 0 point
x When the power supply is turned ON under these conditions, an error occurs.
4-1. Operation Mode Setting