890CS & 890CD Common Bus Units
Page 4-40 890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
SET-UP PARAMETERS
PREF 6511/6901
Display
Default Brief Description V/Hz
SV Vector
Required parameters for each control mode are shown shaded.
102.01
RUN STOP
MODE
0 : RUN RAMP
1 : COAST
2 : DC INJECTION
3 : STOP RAMP
Selects the stopping
mode used by the drive
x x x
103.01
JOG SETPOINT
10.0 % Drive speed setpoint
whilst jogging
(percentage of MAX
SPEED)
x x x
21.01
V/F SHAPE
0 : LINEAR LAW
1 : FAN LAW
2 : USER DEFINED
Sets the type of volts to
frequency template
that is used to flux the
motor
x x x
70.01
QUADRATIC
TORQUE
0 : FALSE
1 : TRUE
0 : FALSE = Constant
Selects between
Constant or Quadratic
mode of operation
x x x
27.05
MOTOR
CURRENT
product code dependent Enter the motor full
load current from the
motor nameplate
x x x