DOC-0017-03-EN: AC15 Series - Hardware Installation Manual
68 (125) DOC-0017-03-EN-B 04.04.2023
Note: The parameters displayed in this list will vary depending on what settings have been selected
i.e., ‘Motor Type’ & ‘Control Strategy’ parameters.
- Enter values as required (keyparameters listed below only):
Parameter Name
No.
Default Value
Range
Units
Type
Writable
Thermistor Type
0892
0: PTC
0: PTC
1: NTC
ENUM
ALWAYS
Motor Type
0030
0: Induction Motor
0: Induction motor
1: PMAC Motor
ENUM
STOPPED
Control Strategy
0031
0: Volts-Hertz Control
0: Volts-Hertz Control
1: Vector Control
ENUM
STOPPED
2. Motor Nameplate Settings:
a) Induction Motor
To enter the ’Motor Nameplate’ information for an Induction Motor:
- Navigate to the ‘Motor Nameplate’ sub-menu:
Motor Nameplate Level Menu Overview
Onboard Keypad Display
6901 Remote Keypad Display
- Enter values as required:
Parameter Name
No.
Default Value
Range
Units
Type
Writable
Base Frequency
0224
50
1 to 1000
Hz
REAL
STOPPED
Base Voltage
0223
400.00
1 to 1000
V
REAL
STOPPED
Nameplate Speed
0226
1450
0 to 100000
rpm
REAL
STOPPED
Motor Power
0227
0.75
0 to 3000
kW
REAL
STOPPED
Power Factor
0228
0.71
0 to 1
REAL
STOPPED
Rated Current
0222
1.56
0.05 to 10000.0
A
REAL
STOPPED
IM Wiring
0182
0: FALSE
0: FALSE
1: TRUE
BOOL
STOPPED
Note: Setting ‘IM Wiring’ to ‘1’ (TRUE) electronically swaps phases V & W - inverting motor
direction.
b) PMAC Motor
To enter the ’Motor Data PMAC’ information for a PMAC Motor:
- Navigate to the ‘Motor Data PMAC’ sub-menu:
Motor Nameplate Level Menu Overview
Onboard Keypad Display
6901 Remote Keypad Display
SEt
CtrL
nPLA
Setup
Motor Control
Motor Nameplate
SEt
CtrL
PnAC
Setup
Motor Control
Motor Data PMAC