EasyManua.ls Logo

Pentair AK110 - PROGRAMMING SCREEN NAVIGATION: ORP CYCLE TIME (1 of 2)

Pentair AK110
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
66
pH > 7.67-OFF 7.50s
ORP 490 -OFF 700s
_____
69.0f SW1OFFSW2OFF
Main Status Screen
Name:Main Pool
System
>Programming
Service
Data ( 8:441 )
Communications
Security Setup
Wizards
Serial # 123456
Configuration Menu, Programming
AK110 Programming Screen Navigation, ORP Cycle Time (1 of 2)
EnterBack
1:pH, Cycle Time
>2:ORP, Cycle Time
3:Not Used
A:Alarm
P:Pager1
P:Pager2
P:Pager3
P:Pager4
Programming Setup Screen
ORP Cycle, Manual Feed Time
EnterBack
ORP Cycle, Proportional Feed Percent
ORP Cycle, Low ORP Setpoint ORP Cycle, Feed Off if Relay is On
Enter new value
Current: 00:02:00
00:02:00
v-Cancel ^
Manual Feed Time Screen
Use the keypad to enter the manual
sanitizer feed duration.
Press the [Enter] key to confirm or
the down arrow key to cancel.
Enter
Proportional Feed Percent Screen
Use the keypad to enter the
proportional feed percentage.
Press the [Enter] key to confirm or
the down arrow key to cancel.
Enter
Enter new value
Current: 5
5
v-Cancel ^
Enter new value
Current: 700
700
v-Cancel ^
Use the keypad to enter the ORP
setpoint for sanitizer feed control.
Press the [Enter] key to confirm or
the down arrow key to cancel.
Enter
Low ORP Setpoint Screen
Use the keypad to enter the number
of a pH feed control relay to prevent
simultaneous chemical feed.
Press the [Enter] key to confirm or
the down arrow key to cancel.
Feed Off if Relay is On Screen
Enter new value
Current: 1
1
v-Cancel ^
Enter
Enter
ORP Cycle, Low pH Setpoint
Enter new value
Current: 0.00
0.00
v-Cancel ^
Low pH Setpoint Screen
Use the keypad to enter the low pH
value under which the sanitizer will
not feed.
Press the [Enter] key to confirm or
the down arrow key to cancel.
ManualTime 00:02:00<
Proportional% 5
On If ORP< 700
Off If pH> 7.95
Off If pH< 0.00
Off if RLY On 1
Cycle Time 00:02:00
On Limit 00:00:30
Off if Sw1 Off-YES
Off if Sw2 On -NO
SetOvrfeed 00:00:00
Overfeed 03:00:00
ManualTime 00:02:00
Proportional% 5<
On If ORP< 700
Off If pH> 7.95
Off If pH< 0.00
Off if RLY On 1
Cycle Time 00:02:00
On Limit 00:00:30
Off if Sw1 Off-YES
Off if Sw2 On -NO
SetOvrfeed 00:00:00
Overfeed 03:00:00
ManualTime 00:02:00
Proportional% 5
On If ORP< 700<
Off If pH> 7.95
Off If pH< 0.00
Off if RLY On 1
Cycle Time 00:02:00
On Limit 00:00:30
Off if Sw1 Off-YES
Off if Sw2 On -NO
SetOvrfeed 00:00:00
Overfeed 03:00:00
ManualTime 00:02:00
Proportional% 5
On If ORP< 700
Off If pH> 7.95
Off If pH< 0.00<
Off if RLY On 1
Cycle Time 00:02:00
On Limit 00:00:30
Off if Sw1 Off-YES
Off if Sw2 On -NO
SetOvrfeed 00:00:00
Overfeed 03:00:00
ManualTime 00:02:00
Proportional% 5
On If ORP< 700
Off If pH> 7.95
Off If pH< 0.00
Off if RLY On 1<
Cycle Time 00:02:00
On Limit 00:00:30
Off if Sw1 Off-YES
Off if Sw2 On -NO
SetOvrfeed 00:00:00
Overfeed 03:00:00
To ORP Cycle Time (2 of 2)
Note:
The relay 2 programming menu
appears in this format only when
relay 2 has been configured for
"ORP Cycle Time" control.
Enter
Enter new value
Current: 7.95
7.95
v-Cancel ^
Use the keypad to enter the high pH
value over which the sanitizer will
not feed.
Press the [Enter] key to confirm or
the down arrow key to cancel.
High pH Setpoint Screen
ManualTime 00:02:00
Proportional% 5
On If ORP< 700
Off If pH> 7.95<
Off If pH< 0.00
Off if RLY On 1
Cycle Time 00:02:00
On Limit 00:00:30
Off if Sw1 Off-YES
Off if Sw2 On -NO
SetOvrfeed 00:00:00
Overfeed 03:00:00
ORP Cycle, High pH Setpoint
Back
Enter
Enter new value
Current: 7.95
7.95
v-Cancel ^
Use the keypad to enter the high pH
value over which the sanitizer will
not feed.
Press the [Enter] key to confirm or
the down arrow key to cancel.
High pH Setpoint Screen
ManualTime 00:02:00
Proportional% 5
On If ORP< 700
Off If pH> 7.95<
Off If pH< 0.00
Off if RLY On 1
Cycle Time 00:02:00
On Limit 00:00:30
Off if Sw1 Off-YES
Off if Sw2 On -NO
SetOvrfeed 00:00:00
Overfeed 03:00:00
ORP Cycle, High pH Setpoint
AK110 Programming Screen Navigation, ORP Cycle Time, Rev 3 22 Aug 2008