POWER ELECTRONICS
DESCRIPTION OF PROGRAMMING PARAMETERS
139
Screen
Description
Default
value
Range
Function
Set
on
RUN
Ad.80
[17]
Fire mode
selection
None
None
Fire
Mode
Fire
Mode
Test
Fire mode forces the drive to ignore all minor
faults and resets and restarts with major
faults without considering the number of retry
attempts. This action is performed until
equipment destruction if necessary.
The drive runs in Fire mode when this
parameter is set to 1 (Fire Mode)’, and the
multifunction terminal (In. 65-71) configured
for Fire mode is turned on.
OPT.
DESCR.
FUNCTION
0
None
Fire mode is off
1
Fire
Mode
Fire mode enabled. When
the digital input configured
as ‘Fire Mode’, the drive
will start working in this
mode, at the frequency
configured in Ad.81 and
the direction set in Ad.82.
2
Fire
Mode
Test
The drive simulates fire
mode operation for a while.
Then, it stops.
NO
Ad.81
[17]
Fire mode
frequency
60.00Hz
0.00 to
60.00Hz
Set the frequency for drive operation in Fire
mode. The Fire mode frequency takes
priority over the Jog frequency, Multi-step
frequencies, and frequency configured from
keyboard.
NO
Ad.82
[17]
Fire mode
direction
Forward
Forward
Reverse
Set Fire mode direction:
OPT.
DESCR.
FUNCTION
0
Forward
Forward direction.
1
Reverse
Reverse direction.
NO
[
17
] Displayed when Ad.80 is set to 1 (YES).