POWER ELECTRONICS
DESCRIPTION OF PROGRAMMING PARAMETERS
167
Screen
Description
Default
value
Range
Function
Set
on
RUN
In.70
Digital input 6
MultVel-
M
0 to 54
Note: Comes from the previous page.
OPT.
DESCR.
FUNCTION
25
XCEL
Stop
Sets the digital input to
stop acceleration or
deceleration. See Figure
Inputs configuration for
acceleration /
deceleration
26
2ndMotor
Set the digital input as
2nd motor operation,
which is used when a
single drive switch
operates two motors.
34
Pre-Excit
Enable the motor pre-
excitation activation,
before start. The user can
adjust this functionality in
parameters Ad.7, Ad.1
and Ad.13.
38
TimerIN
Set the function for the
temporized digital output.
If option 28 “Timer-Ou” is
selected in OU.31 or
OU.33, the digital output
will be enabled once the
time set in OU.56 has
elapsed. Once this digital
input is disabled, the
digital output will be
disabled once the time
set in OU.57 has elapsed.
Note: Continues on the next page.