POWER ELECTRONICS
DESCRIPTION OF PROGRAMMING PARAMETERS
169
Screen
Description
Default
value
Range
Function
Set
on
RUN
In.71
Digital input 7
Mult Vel-
A
Note: Comes from the previous page.
OPT.
DESCR.
FUNCTION
54
TI
In IP66 equipment, pulse
input TI and Multi-function
terminal P5 share the
same terminal. In this
case, set parameter In.69
to 54(TI).
NO
In.85
Digital input
activation
delay
10ms
0 to
10000m
s
Set the delay time when activating the digital
input. In case any variation occurs within a
smaller time gap, the input will remain
disabled.
YES
In.86
Digital input
deactivation
delay
3ms
0 to
10000m
s
Set the delay time when disabling a digital
input. In case any variations occur within a
smaller time gap, the input will remain
enabled.
YES
In.87
Digital input
contact type
00000
0000000
to
1111111
Adjust each to 0 or 1 according to the following
table:
BIT
DESCR.
0
Contact normally open (YES)
1
Contact normally closed (NC)
The assignment order is P1, P2, , P7
starting from the bit placed farthest to the right.
The number of Digital Inputs varies depending
on the equipment (IP20 drives integrate 7
Digital Inputs and IP66 drives integrate 5).
NO
In.89
DI scan time
1ms
1 to
5000ms
Set the time to wait before refreshing the
digital inputs configured as multireference.
NO