DESCRIPTION OF PROGRAMMING PARAMETERS
Screen
Description
Default
value
Range
Function
Set
on
RUN
In.90
Digital inputs
status
00000
0000000
to
1111111
Shows the status of digital inputs:
BIT
DESCR.
0
Disabled
1
Enabled
The assignment order is P1, P2, …, P7
starting from the bit placed farthest to the right.
The number of Digital Inputs varies depending
on the equipment (IP20 drives integrate 7
Digital Inputs and IP66 drives integrate 5).
NO
In.91
TI Monitor
0.00kHz
0.00 to
50.00
kHz
This parameter shows the pulse frequency in
this input.
NO
In.92
TI Filter
10
0 to
9999
This parameter allows setting the time in which
the pulse input reaches 63% of its nominal
frequency. It is useful when the pulse
frequency is supplied in multiple steps.
YES
In.93
TI minimum
input
frequency
0.00kHz
0.00 to
32.00
kHz
PARÁM.
FUNCTION
In.93
This parameter allows setting
the minimum input frequency
through TI.
In.94
This parameter allows setting
the minimum input frequency
percentage through TI.
In.95
This parameter allows setting
the maximum input frequency
through TI.
In.96
This parameter allows setting
the maximum input frequency
percentage through TI.
See Figure TI configuration.
YES
In.94
TI minimum
input
frequency
percentage
0.00%
0.00 to
100.00%
YES
In.95
TI maximum
input
frequency
32.00kH
z
0.00 to
32.00
kHz
YES
In.96
TI maximum
input
frequency
percentage
100.00%
0.00 to
100.00%
YES
In.97
TI Inverting
N
N
S
This parameter allows inverting the TI signal.
Set this parameter to 1 (NO) if you need a
reverse signal.
YES