POWER ELECTRONICS
DESCRIPTION OF PROGRAMMING PARAMETERS
201
Screen
Description
Default
value
Range
Function
Set on
RUN
Pr.32
No motor fault
level
+5%
1 to
100%
The fault protection if no motor is detected
is a combination of parameters Pr.31-33.
The drive will carry out the action set in
parameter Pr.31 whenever the current
flowing within the motor does not exceed the
value defined in parameter Pr.32 during the
time defined in parameter Pr.33.
YES
Pr.33
No motor fault
delay
3.0s
0.1 to
10.0s
YES
Pr.40
Action in case
of thermo-
electronic fault
None
0 to 2
The drive will carry out one of the following
actions in case of a motor thermo-electronic
fault:
OPT.
DESCR.
FUNCTION
0
None
The ETH function is not
activated.
1
Free-
Run
The drive output is
blocked. The motor coasts
to a halt (free-run).
2
Dec
The drive decelerates the
motor until it stops.
YES
Pr.41
Motor cooling
mode at zero
speed
SELF
SELF
FORCE
D
Select the drive mode of the cooling fan
attached to the motor.
OPT.
DESCR.
FUNCTION
0
SELF
As the cooling fan is
connected to the motor
axis, the cooling effect
varies based on motor
speed. Most universal
induction motors have
this design.
1
FORCED
Additional power is
supplied to operate the
cooling fan. This
provides extended
operation at low speeds.
Motors designed for
drives typically have this
design.
YES