DESCRIPTION OF PROGRAMMING PARAMETERS
Overcurrent
level during
1min
Set the current level which flows
continuously during one minute in %
referenced to the motor nominal current.
The motor nominal current is set in
parameter bA.13. Whenever this limit is over
passed, the thermo-electronic protection will
be enabled, and the action defined in
parameter Pr.40 will be executed.
Continuous
overcurrent
level
Set the overcurrent level under which the
drive is able to work without enabling the
thermo-electronic protection.
Define trip mode in free run.
The drive cuts the output
voltage and allows the
motor free run.
The motor decelerates
and then stops.
Stall prevention can be configured for
acceleration, deceleration, or while
operating a motor at constant speed.
Stall protection during
acceleration.
Stall protection while
operating at a
constant speed.
Stall protection during
deceleration.
Flux braking during
deceleration.