Index S Name Type Description
Max
Objects Attr
5119h 1 Soll-Unterbe‐
triebsart
U32 Setpoint
operating
submode
(0-0..20mA,1-
4..20mA,4
linear
curve,..)
SDO RW
511Ah 1 Ist-Unterbe‐
triebsart
U32 Current oper‐
ating sub‐
mode
SDO RO
511Bh 1 Betrieb‐
smodus
(Automatik
On/Off)
U32 Operating
mode (auto‐
matic on(1)/
off(0))
SDO RW
511Ch 1 Konzentra‐
tionsges‐
teuerter
Betrieb
an/aus
U32 Concentra‐
tion-con‐
trolled opera‐
tion on(1)/
off(0)
SDO RW
511Eh 1 Dauer des
Ansaugens
U16 Priming dura‐
tion in sec
SDO RW
511Fh 1 Batch-Faktor U32 Batch factor
(1-99999)
SDO RW
5122h 1 Kontakt-
Faktor
Float Contact
factor
(0.01-99.99)
SDO RW
5147h 1 Maximale
Hubfrequenz
U16 Maximum
stroke rate
SDO RO
5148h 1 Gesamtbe‐
triebsdauer
U32 Operating
period in sec
SDO RO
5152h 1 Dosiermenge
pro Vollhub
Float Metering
quantity per
full stroke in
ml (stroke
length100%)
SDO RO
5153h 1 Löschbarer
Hubzähler
U32 Deletable
stroke
counter
SDO RW
5154h 1 Löschbarer
Mengen‐
zähler
Float Deletable
volume
counter
SDO RW
Tab. 7: Strings
Index S Name Type Description Objects Attr
5D00h 0 PCO_High‐
estSubIndex
U8 RO
1 Name1 String Pump name RO
2 Name2 String RO
Supplementary Operating Instructions CANopen
24

Table of Contents

Other manuals for ProMinent gamma/ X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ProMinent gamma/ X and is the answer not in the manual?

ProMinent gamma/ X Specifications

General IconGeneral
Protection classIP65
Max. Pressure25 bar
Power supply100-230 V, 50/60 Hz
Material of pump headPVDF, Stainless steel
Temperature range-10 °C to +45 °C
TypeDiaphragm dosing pump
Stroke lengthAdjustable
Stroke frequencymax. 180 strokes/min
Materials in contact with the mediumPVDF, PTFE, stainless steel
ControlManual, external control via contacts or 0/4-20 mA signal
Control OptionsExternal, potential-free contacts, 0/4-20 mA
Dosing Accuracy±2%