EasyManua.ls Logo

ProMinent gamma/ X - Electrical Connection and Terminals

ProMinent gamma/ X
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Tab. 10: *
MANDA mandatory
OPTION optional
CONDIT Conditional mandatory
2.7.1.5 Alarm action area for measurement devices (404 )
Index Sub Name Type Description Categ. Attr
6509h 1 Al1_action=1
warn,=3 err
U8 Level min error RW
6519h 1 Al2_action =0 inac‐
tive
U8 Level min warning RW
6529h 1 Al3_action U8 Batch error RW
6539h 1 Al4_action U8 Cal warning RW
6549h 1 Al5_action U8 Sys error RW
6559h 1 Al6_action U8 Not bus RW
6569h 1 Al7_action U8 add2 RW
6579h 1 Al8_action U8 add3 RW
6600 1 Al_state0_7 U8 0=no error,
1=error (DLT/
Sigma/DF3)
RW
2.7.2 EMERGENCY
Tab. 11: Emergency Object Data:
Byte 0 1 2 3 4 5 6 7
Content* Emergency Error
Code*
Error reg‐
ister*
Manufacturer specific Error Field*
Tab. 12: *
Content (1 Byte): 80h+Node-Id
Emergency Error Code (2 Byte): 0x1000 (0x10xx = Generic Error)
0x0000 (0x00xx = No Error)
Error Register (1001h-content) (1 Byte): 0x81 (Bit #0=Generic Error,Bit #7= Manufacturer
specific)
Manufacturer specific Error Field (5 Byte): Byte #3: Component no. (channel)
Byte #4: Error type
Byte #5: Error class
Byte #6: free
Byte #7: free
Emergency ErrorCode (2 Byte): 0xFF01 (0xFFxx = Device specific, 0x01 = Sigma b)
Supplementary Operating Instructions CANopen
34

Table of Contents

Other manuals for ProMinent gamma/ X

Related product manuals