6.3.3 MBTCP Error Codes
Standard Modbus Exception Code Errors
These error codes are generated or returned on both the Controller and slave
ports. These codes are the standard Modbus errors.
Code
Description
1
Illegal Function
2
Illegal Data Address
3
Illegal Data Value
4
Failure in Associated Device
5
Acknowledge
6
Busy, Rejected Message
MBTCP Client Specific Errors
These error codes are specific to the MBTCP client.
Code
Description
-33
Failed to connect to server specified in command
-35
Wrong message length in the response
-36
MBTCP command response timeout (same as -11)
-37
TCP/IP connection ended before session finished
MBTCP Communication Error Codes
The gateway detects these command-specific error codes during initial command
list loading at gateway power-up or reset and are stored in the Command Error
List memory region.
Code
Description
-2
Timeout while transmitting message
-11
Timeout waiting for response after request (same as -36)
253
Incorrect slave/server address in response
254
Incorrect function code in response
255
Invalid CRC/LRC value in response

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ProSoft Technology PLX3x Series and is the answer not in the manual?

ProSoft Technology PLX3x Series Specifications

General IconGeneral
BrandProSoft Technology
ModelPLX3x Series
CategoryGateway
LanguageEnglish

Related product manuals