SIE Protocol PLX3x Series ♦ Multi-Protocol Gateways
User Manual
Page 172 of 215 ProSoft Technology, Inc.
January 25, 2018
9.3.3 SIE Error Codes
SIE Module Communication Error Codes
Decimal
Hex
Description
1
0x0001
No data from I/O module
3
0x0003
The desired item is not available in the PLC (200 family)
5
0x0005
The desired address is beyond limit for this PLC
6
0x0006
The CPU does not support reading a bit block of length<>1
7
0x0007
Write data size error
10
0x000a
The desired item is not available in the PLC
-123
0xff85
Cannot evaluate the received PDU
-124
0xff84
The PLC returned a packet with no result data
-125
0xff83
The PLC returned an error code not understood by this library
-126
0xff82
This result contains no data
-127
0xff81
Cannot work with an undefined result set
-128
0xff80
Unexpected function code in answer
-129
0xff7f
PLC responds with an unknown data type
-1024
0xfc00
Short packet from PLC
-1025
0xfbff
Timeout when waiting for PLC response
-32767
0x8001
Not allowed in current operating status
-32511
0x8101
Hardware fault
-32509
0x8103
Object access not allowed
-32508
0x8104
Context is not supported. Step7 says: Function not implemented or error in
telegram
-32507
0x8105
Invalid address
-32506
0x8106
Data type not supported
-32505
0x8107
Data type not consistent
-32502
0x810A
Object does not exist
-31999
0x8301
Insufficient CPU memory
-31742
0x8402
CPU already in RUN or already in STOP
-31740
0x8404
Severe error
-31488
0x8500
Incorrect PDU size
-30974
0x8702
Address invalid
-12286
0xd002
Step7: Variant of command is illegal
-12284
0xd004
Step7: Status for this command is illegal
-12127
0xd0A1
Step7: Function is not allowed in the current protection level
-11775
0xd201
Block name syntax error
-11774
0xd202
Syntax error function parameter
-11773
0xd203
Syntax error block type
-11772
0xd204
No linked block in storage medium
-11771
0xd205
Object already exists

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ProSoft Technology PLX3x Series and is the answer not in the manual?

ProSoft Technology PLX3x Series Specifications

General IconGeneral
BrandProSoft Technology
ModelPLX3x Series
CategoryGateway
LanguageEnglish

Related product manuals