EasyManua.ls Logo

ProSoft Technology PLX3x Series

ProSoft Technology PLX3x Series
215 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PLX3x Series Multi-Protocol Gateways EIP Protocol
User Manual
ProSoft Technology, Inc. Page 87 of 215
January 25, 2018
Encapsulated PCCC Read Message
Read commands transfer data from the gateway to a processor. The gateway
supports the encapsulated PCCC commands:
PLC2 Unprotected Read
PLC5 Typed Read
PLC5 Word Range Read
PLC Typed Read
The following diagram shows an example rung that executes a read command.
1 In the Message Configuration dialog box, define the data set to be transferred
from the processor to the gateway as shown in the following image.
2 Complete the dialog box for the data area to be transferred.
o For PLC5 and SLC messages, set the SOURCE ELEMENT to an element in
a data file (such as, N10:0).
o For the PLC2 Unprotected Read message, set the SOURCE ELEMENT to
the address in the gateway’s internal database. This cannot be set to a
value less than ten. This is not a limitation of the gateway but of the
RSLogix software.

Table of Contents

Related product manuals