Enter program mode by keying in 1997 and pressing ENTER. Once in program mode
you will need to program both a High Floc alarm relay and set up the parameters in
the new Floc alarm menu option. Assigning an alarm relay to this new feature to alert
you of a high floc presence, also allows you to view on the units trace screen the area
box monitored by the Floc alarm parameters. How to set this alarm relay feature is
explained in ‘Relay parameters’. The parameters required to setup a High Floc alarm
are detailed in the ‘Floc Alarm section.
Floc Alarm menu
Point 2
Point 1
P161 End Distance
P160 Start Distance
P162 Level
P163 % of Intrusion
P164 On Delay
P165 Off Delay
Point 1
P1161 End Distance
P1160 Start Distance
P1162 Level
P1163 % of Intrusion
P1164 On Delay
P1165 Off Delay
Point 2