34 WiNG-MGR User Guide 800.518.1519
3 Web Interface
Battery Run Hours Enter the number of hours the sensor has been running. Set this
value to 0 each time you replace the battery if you are manually
tracking battery life.
Battery Hour Limit Designate the number of hours the battery on the sensor can run
before a battery alarm notification is triggered.
Alarm Notifications
Temp Over Enter a high temperature alarm threshold - if the temperature rises
above this value, a high temperature alarm is generated.
Temp Under Enter a low temperature alarm threshold - if the temperature drops
below this value, a low temperature alarm is generated.
Humidity Over Enter a high humidity alarm threshold - if the humidity rises above
this value, a high humidity alarm is generated.
Humidity Under Enter a low humidity alarm threshold - if the humidity drops below
this value, a low humidity alarm is generated.
Leak Threshold This number represents the uA of current that must be present on
the leak detection sensing cable in order to trigger an alarm.
If you are seeing a large number of false alarms, even after
cleaning the cable, our tech support staff may work with you to
adjust this threshold.
Default = 4
Alarm Delay The number of seconds that pass between the time the system
goes into alarm and the time that alarm is annunciated.
Relay Upon Alarm If the sensor goes into alarm, will it activate a relay? If so, designate
which relay or relays it will activate, and check the appropriate
boxes for which conditions the relay should be activated.
Default = None
Warning Notifications
Temp Over Enter a high temperature warning threshold - if the temperature
rises above this value, a high temperature warning is generated.
Temp Under Enter a low temperature warning threshold - if the temperature
drops below this value, a low temperature warning is generated.
Humidity Over Enter a high humidity warning threshold - if the humidity rises above
this value, a high humidity warning is generated.
Humidity Under Enter a low humidity warning threshold - if the humidity drops below
this value, a low humidity warning is generated.
Warning Delay The number of seconds that pass between the time the system
goes into a warning state and the time that warning is annunciated.
Gain/Offset Settings - Applicable only for WiNG-ANLG analog sensors. Using the formulas
below, adjust the gain and offset values approproately to fine tune your sensor’s accuracy.
Option Description
Table 3.4
Individual Sensor Page - Sensor Configuration Tab Options