Appendix B: Product Certifications
September 2015
220
Product Certifications
I1 ATEX Intrinsic Safety and Dust
Certificate: BAS97ATEX1089X; Baseefa11ATEX0275X
Standards: EN60079-0:2012, EN60079-11:2012,
EN60079-31:2009
Markings: HART: II 1 G Ex ia IIC T5/T4 Ga,
T5(-60 °C
T
a
+40 °C),
T4(-60 °C
T
a
+70 °C)
Fieldbus/PROFIBUS: II 1 G Ex ia IIC Ga
T4(-60 °C
T
a
+60 °C)
DUST: II 1 D Ex ta IIIC T95 °C T
500
105 °C
Da (-20 °C
T
a
+85 °C)
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V
insulation test required by clause 6.3.12 of
EN60079-11:2012. This must be taken into account
when installing the apparatus.
2. The enclosure may be made of aluminum alloy and
given a protective polyurethane paint finish; however
care should be taken to protect it from impact or
abrasion if located in Zone 0.
3. Some variants of the equipment have reduced markings
on the nameplate. Refer to the Certificate for full
equipment marking.
IA ATEX FISCO
Certificate: BAS97ATEX1089X
Standards: EN60079-0:2012, EN60079-11:2009
Markings: II 1 G Ex ia IIC T4 Ga (-60 °C
T
a
+60 °C)
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V
insulation test required by clause 6.3.12 of
EN60079-11:2012. This must be taken into account
when installing the apparatus.
2. The enclosure may be made of aluminum alloy and
given a protective polyurethane paint finish; however
care should be taken to protect it from impact or
abrasion if located in Zone 0.
N1 ATEX Type n and Dust
Certificate: BAS00ATEX3105X; Baseefa11ATEX0275X
Standards: EN60079-0:2012, EN60079-15:2010,
EN60079-31:2009
Markings: II 3 G Ex nA IIC T5 Gc
(-40 °C
T
a
+70 °C);
II 1 D Ex ta IIIC T95 °C T
500
105 °C Da
(-20 °C
T
a
+85 °C)
Special Conditions for Safe Use (X):
1. This apparatus is not capable of withstanding the 500V
insulation test that is required by clause 6.8.1 of
EN60079-15. This must be taken into account when
installing the apparatus.
2. Some variants of the equipment have reduced markings
on the nameplate. Refer to the Certificate for full
equipment marking.
International
E7 IECEx Flameproof and Dust
Certificate: IECEx KEM 09.0034X; IECEx BAS 10.0034X
Standards: IEC60079-0:2011, IEC60079-1:2007-04,
IEC60079-26:2006, IEC60079-31:2008
Markings: Ex d IIC T6/T5 Ga/Gb,
T6(-50 °C
T
a
+65 °C),
T5(-50 °C
T
a
+80 °C);
Ex ta IIIC T95 °C T
500
105 °C Da
(-20 °C
T
a
+85 °C)
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation,
maintenance and use shall take into account the
environmental conditions to which the diaphragm will
be subjected. The manufacturer’s instructions for
installation and maintenance shall be followed in detail
to assure safety during its expected lifetime.
2. For information on the dimensions of the flameproof
joints the manufacturer shall be contacted.
3. Some variants of the equipment have reduced markings
on the nameplate. Refer to the Certificate for full
equipment marking.
Table 2. Input Parameters
Parameters
HART Fieldbus/PROFIBUS
Voltage U
i
30 V 30 V
Current I
i
200 mA 300 mA
Power P
i
0.9 W 1.3 W
Capacitance C
i
0.012 F 0 F
Inductance L
i
0 mH 0 mH
Table 3. Input Parameters
Parameters
FISCO
Voltage U
i
17.5 V
Current I
i
380 mA
Power P
i
5.32 W
Capacitance C
i
< 5 nF
Inductance L
i
< 10 F
Table 4. Process Temperature
Temperature class Process temperature
T6 -50 °C to +65 °C
T5 -50 °C to +80 °C