EbV Product documentation THETA NORM/UNIT
5-3
5.1.2.3 "Night-time Room Temperature" Key
This key sets the reduced room temperature setpoint in the AUTOMATIC MODE
between the heating cycles as well as during the ABSENT and RED.HEATING
operating modes.
In control mode 1 the set point is identical for all the heating circuits. In control mode
2 the setpoint is individual for the circuits concerned.
NOTE! Connected wall modules are not affected. The setting of the daytime room
temperature is carried out solely by the wall module concerned.
Setting:
Press the ¦ key
Set the flashing specified room temperature by turning the rotary
pushbutton î to the desired value.
Confirm the set value by pressing either the ¦ key or the rotary
pushbutton î.
Alternatively: the value can be acquired automatically after the set INFO
TIME
Factory setting 16 °C
Setting range 5 ... 30 °C
5.1.2.4 "Daytime DHW Temperature" Key
This key sets the daytime DHW temperature in the AUTOMATIC MODE as well as
during the PARTY and HEATING operating modes. This setting value also applies
to domestic hot water only mode (manual summer mode).
NOTE! Thi setpoint is the starting value for the individual temperature setting during the
DHW cycles (= cycle temperatures) in the "time programs" menu.
If these values differ from the starting value, they are corrected with the requisite
amount of the adjustment if a subsequent adjustment of the setpoint is made.
¦
ROOM NIGHT
o
c
16.0
§