EbV Product documentation THETA NORM/UNIT
8-21
8.2.1.2 Heating Circuit Reduced Mode
Function: During reduced mode you can choose between two operating modes:
RED: reduced mode
The direct heating circuit’s heating circuit pump remains active during reduced mode
(see Switching Time Program). The flow temperature is determined by the relevant
reduced heating characteristic according to the decreased room setpoint. The set
minimum temperature will be maintained.
Application:
Buildings with low insulation values and high heat losses.
ECO: switch-off mode:
During reduced mode the direct heating circuit is completely switched off if the
outside temperature exceeds the set frost protection limit. The heat generator
minimum temperature limit is deactivated. The heating circuit pump is switched off
with a short delay in order to avoid a safety switch-off owing to the post heating of the
heat generator (extended pump running time).
If the outside temperature falls below the specified frost protection limit, the controller
switches from switch-off mode (ECO) to reduced mode (RED) and the heating circuit
temperature is adjusted according to the set reduced characteristic considering the
set heat generator minimum temperature settings.
Application:
Buildings with high insulation values.
Important:
The mode set here applies also for the ASENT und CONSTANT REDUCED
operating modes.
Operation:
Note on operation Key / parameter tree Parameter
Setting reduced mode UNMIXED CIRCUIT
or
MIX. VALVE-1
or
MIX. VALVE-2
RED. HEATING

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rotex Controller Series and is the answer not in the manual?

Rotex Controller Series Specifications

General IconGeneral
BrandRotex
ModelController Series
CategoryController
LanguageEnglish

Related product manuals