EbV Product documentation THETA NORM/UNIT
5-36
5.4.5.2 Legionella protection day
Factory preset: OFF
Setting range: OFF, MO...SU, ALL
Setting values: OFF: The legionella protection function is not active.
MO...SU: The legionella protection is activated on the selected
weekday at the Llegionella protection time set by the heating
specialist with a different parameter.
ALL: The legionella protection function is activated every day
at the Legionella protection time.
Function:
This parameter serves to prevent a legionella outbreak in the hot water tank and is
activated on the selected weekday or every day at 02:00 hrs. If the DHW temperature
is below 65°C, the hot water tank is reloaded.
Note: If a DHW thermostat is used to determine the water heater temperature, this
parameter is skipped.
5.4.6 Unmixed Circuit / Mixed Circuit 1 / Mixed Circuit 2 Menu
This level comprises all parameters which are necessary to program the heating
circuits with the exception of the time programs. A maximum of 1 unmixed circuit and
2 mixed circuits (mixed circuit 1 and mixed circuit 2) are available per controller as
heating circuits.
The heating circuit parameters described below are available for each heating circuit
and are to be set separately.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rotex Controller Series and is the answer not in the manual?

Rotex Controller Series Specifications

General IconGeneral
BrandRotex
ModelController Series
CategoryController
LanguageEnglish

Related product manuals