EbV Product documentation THETA NORM/UNIT
5-33
5.4.4.3 Control mode
Factory preset: 1
Setting range 1, 2
This parameter determines the control mode and has effects on the:
- Operating mode selected with the operating mode key ¢
- Daytime temperature selected with the "daytime temperature" key ¥
- Nighttime temperature selected with the "night-time temperature" key ¦
concerning the effect on the different heating circuits.
Setting values: 1: The selected setting (operating mode, daytime temperature,
night-time temperature) applies for all the heating circuits
2: Each heating circuit can be assigned its own setting (operating mode,
daytime temperature, night-time temperature).
5.4.4.3.1 Separate Control Mode Daytime Temperature
Function:
In this operating mode, the relevant setpoint applies only to the selected HC (=
unmixed circuit), MC 1 (= mixed circuit 1) or MC 2 (= mixed circuit 2)
Setting:
Press ¥ key
Select the desired heating circuit, HC, MC-1 or MC-2, using the rotary pushbutton
Confirm the selected circuit by pressing the rotary pushbutton
Set the flashing room temperature value by turning the rotary pushbutton to the
desired value.
Confirm set value by pressing ¥ or î , press again: return to standard display
Alternatively the value can be confirmed by automatic exit after the set time.
¥