EbV Product documentation THETA NORM/UNIT
6-2
6.2 Controller configuration
6.2.1 Complete reset
To reset all settings, the device can be reset completely.
Press the
¢, ¥, ¦ and § keys simultaneously until the controller boots again.
6.2.2 Basic settings and parameter preselection
CAUTION The setting options deacribed below affect the operation. After the adaptation,
the end user must be informed about the changed operation.
6.2.2.1 Switching Time Program Enabling
Description: This controller family has three separate switching time programs for each heating
circuit.
When supplied, only one switching time program is enabled. The use of only a single
switching time program for a wide range of applications makes it possible to simplify
operating.
6.2.2.2 Suppressing the cycle temperature on Time program level
When programming switching times, the specialist can set a system parameter to suppress the cycle
temperature.
Function: If the setting is "ON", the operation is not changed. If the setting is "OFF", the
following reaction occurs:
• All cycle temperatures are suppressed during switching time pro-gramming
• Any offset will not affect the set temperature to be corrected
• All connected room devices react identically to parameter changes in the central
device
Operation:
Note on operation Key / parameter tree Parameter
Time programming TIMEPROGRAMS
Enabling separate
programs
SYSTEM PROGRAM
Operation:
Note on operation Key / parameter tree Parameter
Time program cycle temperature SYSTEM PARAMETER 18