47
8.3 Other faults
8.3.1 Boiler controller is noisy when igniting
Gas supply pressure too high.
The home pressure controller may be faulty. Contact the energy company.
Incorrect ignition distance.
Check the ignition pin distance with the checking mold.
Replace the ignition pin.
Gas/air regulation not correctly configured.
Check the setting, see Gas air regulation par.7.7 and par. 7.8.
Check the ignition pin distance with the checking mold.
Check and/or replace ignition cable.
Replace the ignition unit on the gas block. Replace the ignition pin.
8.3.2 Boiler controller resonates
Gas supply pressure too low. Lower than 20
mbar.
The home pressure controller may be faulty. Contact the energy company.
Recirculation combustion gases.
Check the combustion gas outlet and the air supply system.
Gas/air regulation not configured correctly.
Check the setting, see Gas air regulation par.7.7 and par. 7.8.
Boiler controller gasket faulty.
Replace the boiler controller gasket.
Boiler controller faulty.
Replace the boiler controller.
8.3.3 No heating (CH)
The service display shows nothing.
Check whether the plug is in the socket.
The service display shows nothing.
Check the fuse, see Electrical diagram par. 10.1
The service display shows a hyphen (
-
). The
boiler is off.
Switch on the boiler with the button.
Room thermostat/weather dependent regulation
not connected or faulty.
Check the wiring.
Check OpenTherm, On/off connection of the unit, or the connection between CH
boiler and RF room thermostat .Replace the thermostat.
Replace the weather-dependent regulation.
Pump is not running. Display shows 80 and 1.
Check the electricity supply.
Check connector X2 and X4.
Checking mold ignition pin position
Pin must not touch test tool