EB 5573-1 EN 105
System-wide functions
Parameters WE Parameters: value range
Minimum ow temperature set point HC
for binary demand processing
40.0°C PA1 > P10: 5.0 to 150.0°C
Demand processing, 0to 10 V
Regardless of the operating mode set for RK1 control circuit (except for manual mode), the
controller regulates the ow temperature at least to the temperature corresponding with the 0
to 10V signal connected to terminals 11/12.
Functions WE Conguration
Demand processing 0 CO1 > F15 - 1
Demand processing, 0to 10 V 0
0°C
120°C
CO1>F16 - 1
Lower transmission range: 0 to 150°C
Upper transmission range: 0 to 150°C
Binary demand processing 0 CO1 > F17 - 0
Parameters WE Parameters: value range
Set point boost (pre-control circuit) 5.0°C PA1 > P15: 0.0 to 50.0°C
8.11 Creep feed rate limitation with a binary input
It is possible to report to the controller when the creep feed rate has fallen below a certain
level by using a limit switch of the primary valve connected to the terminals 04/12 or to in-
put RüF1. Either the open ('Active when BI=' OFF) or closed binary input ('Active when BI ='
ON) can be congured at terminals 04/12 to indicate that the creep feed rate has fallen be-
low a certain level. Only the closed binary input at RüF1 can be processed. Shortly after the
alert, the controller closes the valve RK1. As soon as the ow temperature falls below the set
point by more than 5°C after the valve has been closed, control operation is started again.
Functions WE Conguration
Creep feed rate limitation 0
Binary
ON
CO5 > F12 - 1
Switching mode: Binary (terminals 04/12), ana-
log (RüF1)
Active when BI =: ON, OFF