EB 5573-1 EN 79
Functions of the heating circuit
Note:
The buffer tank control circuit is deactivated as described in section6.4. When pre-
dened gradients of heating characteristic (CO1 > F11-0) are used, night mode is
not possible in the buffer tank control circuit. In contrast to an active four-point char-
acteristic (CO1 > F11-1): in this case, a four-point characteristic exists for day and
night modes.
Functions WE Conguration
Speed reduction of charging pump based
on charging progress
0
40°C
50 °C
2V
CO1 > F21
Start speed reduction: 5 to 90°C
Stop speed reduction: 5 to 90°C
Min. speed signal: 0 to 10V
Parameters WE Parameters: value range
Solar circuit pump ON 10.0°C PA4 > P10: 1.0 to 30.0°C
Solar circuit pump OFF 3.0°C PA4 > P11: 0.0 to 30.0°C
Max. storage tank temperature 80.0°C PA4 > P12: 20.0 to 90.0°C
Start temperature for boiler pump 60.0°C PA5 > P01: 20.0 to 90.0°C
Boiler pump hysteresis 5.0°C PA5 > P02: 0.0 to 30.0°C
6.6 Summer mode
Summer mode is activated depending on the mean daytime temperature (measured between
7.00h and 22.00h) during the adjusted summer time period. If the mean daytime tempera-
ture exceeds the 'Boost' on the number of successive days set in 'No. days until activation',
summer mode is activated on the following day. This means that the valves in all heating cir-
cuits are closed and the circulation pumps are switched off after t = 2 x valve transit time. If
the mean daytime temperature falls below the 'Limit' on the number of successive days set in
'No. days until deactivation', summer mode is deactivated on the following day.
Functions WE Conguration
Summer mode 0
01.06 - 30.09
2
1
18.0°C
CO5 > F04 - 1
Time: Adjustable as required
No. days until activation: 1 to 3
No. days until deactivation: 1 to 3
Limit: 0.0 to 30.0°C