EB 5573-1 EN 83
Functions of the heating circuit
Functions WE Conguration
Room sensor 0 CO1, 2 > F01 - 1
Flash adaptation 0
20min
0.0
CO1, 2>F09 - 1
Cycle time: 0 to 100min
KP (gain): 0.0 to 25.0
Parameters WE Switch position: value range
Day set point 20.0°C
: –5.0 to 150.0°C
Night set point 15,0°C
: –5.0 to 150.0°C
6.10.1 Flash adaptation without outdoor sensor (based on room
temperature)
The ow temperature control starts with 'Day set point' for ow in rated operation or with
'Night set point' for ow in reduced operation as no set points calculated using characteris-
tics exist without an outdoor sensor. The 'Cycle time' determines the intervals at which the
ow temperature set point is corrected by 1°C. The heating is then always switched off as
soon as the room temperature exceeds the 'Day set point' or 'Night set point' by 2°C. Heat-
ing rst starts again when the room has cooled off and the room temperature is 1°C above
the set point. A 'KP (gain)' set to a value other than 0 causes a direct increase/decrease in
ow temperature set point when a sudden deviation in room temperature arises. A 'KP
(gain)' setting of 10.0 is recommended.
Functions WE Conguration
Room sensor 0 CO1, 2 > F01 - 1
Outdoor sensor CO1 > F02 - 0
Flash adaptation 0
20min
0.0
CO1, 2>F09 - 1
Cycle time: 1 to 100min
KP (gain): 0.0 to 25.0
Parameters WE Switch position: value range
Day set point 20.0°C
: –5.0 to 150.0°C
Night set point 15,0°C
: –5.0 to 150.0°C
Parameters WE Parameters: value range
Flow set point (day) 50.0°C PA1, 2 > P03: –5.0 to 150.0°C
Flow set point (night) 30.0°C PA1, 2 > P04: –5.0 to 150.0°C