EB 5573-1 EN 83
Functions of the heating circuit
Functions WE Conguration
Room sensor 0 CO1, 2 > F01 - 1
Flash adaptation 0
20min
0.0
CO1, 2>F09 - 1
Cycle time: 0 to 100min
KP (gain): 0.0 to 25.0
Parameters WE Switch position: value range
Day set point 20.0°C
: –5.0 to 150.0°C
Night set point 15,0°C
: –5.0 to 150.0°C
6.10.1 Flash adaptation without outdoor sensor (based on room
temperature)
The ow temperature control starts with 'Day set point' for ow in rated operation or with
'Night set point' for ow in reduced operation as no set points calculated using characteris-
tics exist without an outdoor sensor. The 'Cycle time' determines the intervals at which the
ow temperature set point is corrected by 1°C. The heating is then always switched off as
soon as the room temperature exceeds the 'Day set point' or 'Night set point' by 2°C. Heat-
ing rst starts again when the room has cooled off and the room temperature is 1°C above
the set point. A 'KP (gain)' set to a value other than 0 causes a direct increase/decrease in
ow temperature set point when a sudden deviation in room temperature arises. A 'KP
(gain)' setting of 10.0 is recommended.
Functions WE Conguration
Room sensor 0 CO1, 2 > F01 - 1
Outdoor sensor CO1 > F02 - 0
Flash adaptation 0
20min
0.0
CO1, 2>F09 - 1
Cycle time: 1 to 100min
KP (gain): 0.0 to 25.0
Parameters WE Switch position: value range
Day set point 20.0°C
: –5.0 to 150.0°C
Night set point 15,0°C
: –5.0 to 150.0°C
Parameters WE Parameters: value range
Flow set point (day) 50.0°C PA1, 2 > P03: –5.0 to 150.0°C
Flow set point (night) 30.0°C PA1, 2 > P04: –5.0 to 150.0°C