Functions of the heating circuit
6 Functions of the heating circuit
Which controller functions are available depends on the selected system code number (Anl).
6.1 Weather-compensated control
When weather-compensated control is used, the ow temperature is controlled based on the
outdoor temperature. The heating characteristic in the controller denes the ow temperature
set point as a function of the outdoor temperature (seeFig. 3). The outdoor temperature re-
quired for weather-compensated control can either be measured at an outdoor sensor or re-
ceived over the 0 to 10V input.
20
30
0.2
2.4
2.62.93.2
2.2
2.0
1.8
1.6
1.4
1.2
1.0
0.8
0.4
0.6
40
50
60
70
80
90
–24 –28 –32 –36 –40
t
VL
t
A
t
VL
Flow temperature
t
A
Outdoor temperature
Fig. 3: Gradient characteristics
Functions WE Conguration
Outdoor sensor 0 CO1 > F02 - 1
0 to 10V signal for outdoor temperature 0
Input
–20°C
50°C
CO5>F23 - 1
Direction: Input
Lower transmission range: –30 to 100°C
Upper transmission range: –30 to 100°C