Operational faults
Error message Meaning Decimal value
Err 1 Sensor failure 1 1
Err 2 2
Err 3 Disinfection temperature not reached 4
Err 4 Max. charging temperature reached 8
Err 5 16
Err 6 Temperature monitor alarm 32 32
Err 7 Unauthorized access occurred 64
Err 8 128
Err 9 256
Total
Example: Value of error status register when a sensor fails and a temperature monitoring
alarm =
33
9.5 Alarm notication by text message
If a dial-up modem is connected to RS-232/modem communication module (refer to sec-
tion10.1), the controller can send a text message to a mobile phone when an error occurs.
As soon as a fault has been registered in the error status register, the text message indicating
a controller fault is sent. On the mobile phone, the following error message is displayed:
[Date] [Time]
[Phone number of the controller]
Controller malfunction
TROVIS 5573 # [Controller ID of defective con-
troller]
The time stamp [Date], [Time] is added by the text messaging center, not by the controller. If
an error message is transmitted to a controller equipped with a dial-up modem, the controller
ID of the defective controller is sent, instead the controller ID of the “modem controller. A de-
tailed error message is not available.
Note:
The controller ID is indicated in the extended operating level under Info 2 as the serial
number (see page9).