Functions of the DHW circuit
7.5 Intermediate heating
This function can only be activated in systems Anl 2.x, 4.1 and 4.5.
With the setting CO4 > F07-1, heating operation of the UP1 heating circuit is reactivated
for a period of 10 minutes after 20 minutes of priority operation (heating deactivated during
DHW heating). By setting CO4 > F07-0, storage tank charging is given unlimited priority
over the heating operation in the UP1 heating circuit.
Functions WE Conguration
Intermediate heating 1 CO4 > F07 - 1
7.6 Parallel pump operation
This function can only be activated in systems Anl 2.1 to 2.1, 4.1 and 4.5.
When CO4 > F06 - 1, the circulation pump UP1 remains activated during DHW heating.
This does not include operating situations during which the current ow temperature demand
of the pump circuit is lower than the adjusted 'Temperature limit'. In this case, the controller
applies priority operation, if necessary with intermediate heating. Once a parallel pump op-
eration cycle has been activated and the time period set in 'Stop' has elapsed, system devia-
tions greater than 5°C cause the controller to suspend parallel operation for 10 minutes and
to apply priority operation.
Setting 'Stop' to 0min leads to a parallel operation once initiated remaining regardless of a
deviation.
Functions WE Conguration
Parallel pump operation 0
10min
40.0°C
CO4>F06 - 1
Stop: 0 to 10min
Temperature limit: 20.0 to 90.0°C
7.7 Speed control of charging pump
An active speed control of the charging pump (CO4 > F21 - 1) causes the storage tank sen-
sor 2 to be activated, however, in combination with CO4 > F02 - 0 only to measure the
speed control.
When the storage tank charging pump SLP is switched on, the speed control of the pump is
activated: if the temperature at the storage tank sensor 2 is low at the beginning, a 10V sig-
nal is issued at Y1. If the temperature at SF2 reaches the value entered in 'Start speed reduc-
tion', the signal level at Y1 is reduced within the range between the limits entered in 'Start