EB 5573-1 EN 85
Functions of the heating circuit
Functions WE Conguration
Outdoor sensor CO1 > F02 - 1
Cooling control 0 CO1, 2 > F04 - 1
Four-point characteristic 0 CO1, 2 > F11 - 1
Parameters WE Parameters: value range
Outdoor temperature Point 1
Point 2
Point 3
Point 4
5.0°C
15.0°C
25.0°C
30.0°C
PA1, 2 > P05: –50.0 to 50.0°C
Flow temperature Point 1
Point 2
Point 3
Point 4
20.0°C
15.0°C
10.0°C
5.0°C
PA1, 2 > P05: –5.0 to 150.0°C
Reduced ow temperature Point 1
Point 2
Point 3
Point 4
30.0°C
25.0°C
20.0°C
15.0°C
PA1, 2 > P05: –5.0 to 150.0°C
Base point for return ow temperature 65.0°C PA1, 2 > P13: 5.0 to 90.0°C
Note:
The limiting factors 'KP' of the return ow sensor (CO1, 2 > F03) functions apply
during cooling control as well.
Cooling control without outdoor sensor
When the cooling control function is activated in a control circuit without outdoor sensor, only
the adjustment limits for the day and night set points at the rotary switch as well as the 'Base
point for return ow temperature' can be adjusted in PA1 and/or PA2.
Functions WE Conguration
Outdoor sensor CO1 > F02 - 0
Cooling control 0 CO1, 2 > F04 - 1
Parameters WE Switch position: value range
Flow set point (day) 50.0°C
: –5.0 to 150.0°C
Flow set point (night) 30.0°C
: –5.0 to 150.0°C