10-24
10.7.8 Accel/Decel Change frequency
LED
display
Parameter
name
Setting
range
Description
Factory
defaults
Adj.
During
run
H69
Accel/Decel
Change
Frequency
0 ~
400Hz
Accel/Decel change frequency
setting
0Hz X
I34
Multi time
Accel 1
0~ 6000
[sec]
-
3.0
O
I35
Multi time
Decel 1
- 3.0
ACC
Accel time
0 ~ 6000
[sec]
During Multi-Accel/Decel operation,
this parameter serves as
Accel/Decel time 0.
5.0
O
dEC
Decel time
10.0
O
- The output frequency is less than this set value; the Sinus M changes the speed based on the
1st Acc/Dec time values. If higher than this value, it takes the Acc/Dec time in Drv Group.
- If even one of the Multifunctional digital input is set to XCEL,M,H, then this function should be
invalid.
Parameter settings
Ref
source
Keypad
Control
mode
V/F
Ref value
50Hz
H69
25Hz
Acc time
10.0 sec
I34
20.0 sec
Dec time
20.0 sec
I35
40.0 sec