15.2 Inverter Efficiency and Heating Loss
Measured conditions: 50Hz; 100% Current Load; Default Carrier Frequency.
Note: The inverter efficiency is computed by considering the SMPS power consumption.
0001 0002 0003 0005 0007 0011 0014 0017 0020 0025 0030
Efficiency % 95.3 95.5 98.4 97.2 97.2 98.4 98.9 97.0 95.2 95.7 96.2
Heating Loss
W 13 28 18 56 106 73 70 290 683 759 799
kcal 11 24 15 48 91 63 61 249 587 799 687
0001 0002 0003 0005 0007 0011 0014 0017 0020 0025 0030
Efficiency % 96.2 96.2 97.5 97.6 97.5 98.2 98.3 97.0 95.7 95.7 95.2
Heating Loss
W 9 22 32 47 94 84 113 293 608 759 1019
kcal 8 19 27 40 81 72 97 252 523 652 877