10-44
Inverter
Remote
keypad
Parameter Write(H92)
Parameter Read(H91)
10.24 Parameter read/write
Group Display Parameter Name Setting Range Default Unit
Function
group 2
H91 [Parameter read] 1
0 ~ 1
0
H92 [Parameter write] 1
0 ~ 1
0
Used to read/write Inverter Parameters using remote keypad.
Caution:
Take caution when Parameter write (H92) is executed. By doing this, operation inverter
parameters are cleared and the parameters of remote the remote keypad are copied into the
inverter.
Parameter read
Step Note Keypad display
1 Move to H91 code. H91
2 Press Enter () key once. 0
3 Press Up () key once. rd
4 Press Enter () key twice. rd
5 H91 is displayed when Parameter read is finished. H91
Parameter write
Step Note Keypad display
1 Move to H92 code. H92
2 Press Enter () key once. 0
3 Press Up () key once. Wr
4 Press Enter () key twice. Wr
5 H91 is displayed when Parameter read is finished. H92
During parameter reading (H91), the display of the remote keypad shows “rd”(Read) and
“vr”(Verify), whereas during parameter writing (H92) the display only shows “wr”(Write).