9.5 V/F control
Linear V/F pattern operation
Group Code Parameter Name Setting Range Initial Unit
Function group 1 F22
- 30 ~ 400 50.00 Hz
F23 [Start frequency] - 0.1 ~ 10.0 0.50 Hz
F30 [V/F pattern] 0
0 ~ 2 0
Function group 2 H40 [Control mode select] - 0 ~ 3 0
This pattern maintains a linear Volts/frequency ratio from F23 - [Start frequency] to F22-
[Base frequency]. This is appropriate for constant torque applications.
Base Frequency: Inverter outputs its rated voltage at this level. Enter the motor nameplate frequency.
Start Frequency: Inverter starts to output its voltage at this level.
Square V/F pattern
Group Code Parameter Name Setting Range Initial Unit
Function
F30 [V/F pattern] 1
0 ~ 2 0
This pattern maintains squared volts/hertz ratio. Appropriate applications are fans, pumps,
Run
command
Freq.
Start freq.
Base freq.
Voltage
Inverter rated
voltage
Freq.
Base freq.
100%
Voltage