10.13 Operating sound select (Carrier frequency change)
Group Display Parameter Name Setting Range Default Unit
H39 [Carrier frequency] -
1 ~ 15 3 kHz
This parameter affects the sound of the inverter during operation.
When setting carrier frequency
high
Motor sound reduced
Inverter heat loss increased
Inverter noise increased
Inverter leakage current
increased
10.14 2
nd
motor operation
Group Display Parameter Name Setting Range Default Unit
H81 [2nd motor accel time] - 0 ~ 6000 5.0 sec
H82 [2nd motor decel time] -
10.0 sec
H83 [2nd motor base freq.] - 30 ~ 400 60.00 Hz
H84 [2nd motor V/F pattern] - 0 ~ 2 0
H85
[2nd motor Positive torque
boost]
[2nd motor Negative torque
boost]
[2nd motor stall prevention
level]
[2nd motor electronic thermal
level for 1 min]
[2nd motor electronic thermal
level for continuous operation]
- 50 ~ 200 100 %
H90 [2nd motor rated current] - 1 ~ 50 26.3 A
[Multi-function Input terminal
P1Function select]
[Multi-function Input
terminal P8 Function select]
Set the terminal among Multi-function input P1 through P5 for second motor
operation.
To define the terminal P5 as second motor operation, set I24 to 12.