EasyManua.ls Logo

Santerno Sinus M - 7.1 Drive group

Santerno Sinus M
219 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-2
LED
display
Parameter
name
Setting
range
Description
Factory
defaults
Adj.
during
run
rPM
[Motor RPM]
Displays the number of Motor RPM.
-
-
dCL
[Inverter DC
link voltage]
Displays DC link voltage inside the
inverter.
-
-
vOL [User display
select]
This parameter displays the item
selected at H73- [Monitoring item
select].
vOL -
vOL
Output voltage
POr
Output power
tOr
Torque
nOn
[Fault
Display]
Displays the types of faults, frequency
and operating status at the time of the
fault
-
-
drC
[Direction of
motor
rotation
select]
F, r
Sets the direction of motor rotation
when drv - [Drive mode] is set to 0.
F
O
F
Forward
r
Reverse
drv2
1)
[Drive mode
2]
0 ~ 3
0
Run/Stop via Run/Stop key on the
keypad
1
X
1
Terminal
operation
FX: Motor forward run
RX: Motor reverse run
2
FX: Run/Stop enable
RX: Direction
3
RS485
Communication
Frq2
1)
[Frequency
setting
method 2]
0 ~ 7
0
Digital
Keypad setting 1
0
X
1
Keypad setting 2
2
Analog
V1 1: 10 ~ +10 [V]
3
V1 2: 0 ~ +10 [V]
4
Terminal I: 0 ~ 20
[mA]
5
Terminal V1 setting 1
+ Terminal I
6
Terminal V1 setting 2+
Terminal I
7 Digital
RS485
Communication
1)
: Displayed only when one of the Multi-function input terminals 1-8 [I17~I24] is set to “22”.

Table of Contents