Santerno Sinus M - 7.4 I;O group 2

Santerno Sinus M
219 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-22
LED
display
Parameter name
Min/Max
range
Description
Factory
defaults
Adj.
during
run
I56
[Fault relay
output]
0 ~ 7
When
setting the
H26
[Number of
auto restart
try]
When the
trip other
than low
voltage
trip occurs
When the
low
voltage trip
occurs
2
O
Bit 2
Bit 1
Bit 0
0
-
-
-
1
-
-
2
-
-
3
-
4
-
-
5
-
6
-
7
I57
[Output terminal
select when
communication
error occurs]
0 ~ 3
Multi-function
relay
Multi-function
output terminal
0
O
Bit 1
Bit 0
0
-
-
1
-
2
-
3
I59
[Communication
protocol select]
0 ~ 1
Set communication protocol.
0
X
0
Modbus RTU
1 ES BUS
I60
[Inverter number]
1 ~ 250
Set for RS485 communication
1
O
I61
[Baud rate]
0 ~ 4
Select the Baud rate of the RS485.
3
O
0
1200 [bps]
1
2400 [bps]
2
4800 [bps]
3
9600 [bps]
4
19200 [bps]
I62
[Drive mode
select after loss
of frequency
command]
0 ~ 2
It is used when freq command is given
via V1 /I terminal or RS485.
0
O
0 Continuous operation at the
frequency before its command is lost.
1
Free Run stop (Output cut-off)
2
Decel to stop