E6: Error External Event
There is an external noise signal.
Measures : Rectify fault.
Parameter : P06 and O11
Calibration C
C1: LC input
The load cell cable is interrupted, not connected or is improperly connected.
Measures : Check the cabling. If it is as it should be the load cell or the load
cell amplifier may not be working.
Parameter : O 06
C2: Tachometer input
The output frequency of the speed sensor exceeds 3,000Hz.
This situation can only occur with a subsequent change in belt speed (e.g. gears).
Measures : Check the dimensioning of the speed sensor.
If necessary, measure the pulse frequency with an oscilloscope.
Parameter : O 03
Maximum H
H2: Belt Load > MAX
The current belt load exceeded the set limit value.
Measures : Usually none, if the message H4 does not also occur or if
system-specific limits are to be observed.
Parameters : F 07, F 08
H4: LC Input > MAX
The weigh system is overloaded. Measuring errors may occur.
Measures : Check the bin feeder, as the belt load is too large.
Parameters : O08
Event messages
INTECONT® Satus Operating Manual BV-H2346GB / 0833 59