1.17
Date Code 20020501 SEL-2701 Ethernet Processor Instruction Manual
Introduction
Specifications
Specifications
Standard Features and Functions
Indicators
Power/Transmit: Red LED, Power/Tx
Link/Receive: Green LED, Link/Rx
Port A Enabled: Green LED, A
Port B Enabled: Green LED, B
Communication Protocols
Protocol Stacks: TCP/IP, UDP/IP, OSI
File Exchange: FTP
Terminal Server: Telnet
Terminal Client: Telnet
UCA2: GOMSFE 0.91
Optional Features and Functions
Physical Layer
10/100BASE-T: 10/100 Mbps, RJ-45
10BASE-FL: 10 Mbps, ST
100BASE-FX: 100 Mbps, ST
Ratings and Type Tests
Environmental Tests (installed in host)
Operating Temp.: –40° to +70°C (–40° to +158°F)
Type Tests (installed in host)
Cold: IEC 60068-2-1 1990,
EN 60068-2-1 1993, Test Ad, 16 hours at –40 ± 2°C
Dry Heat: IEC 60068-2-2 1974,
EN 60068-2-2 1993, Test Bd, 16 hours at 70 ± 2°C
Damp Heat, Cyclic: IEC 60068-2-30 1980, Test Db, 25º to 55ºC, 6 cycles, 95% humidity
Vibration: IEC 60255-21-1 1988
Vibration Endurance Class 1
Vibration Response Class 2
Shock and Bump: IEC 60255-21-2 1988
Shock Withstand Class 1
Shock Response Class 2
Bump Class 1
IEC 60255-21-3 1993 Class 2 (Single Axis Sine Sweep, 5–35 Hz)
Electrostatic Discharge: IEC 60255-22-2 1996
(see Note) IEC 61000-4-2 1995
10BASE-FL: Level 4
100BASE-FX: Level 4
10/100BASE-T with cable > 92 cm (3 ft): Level 4
10/100BASE-T with cable > 31 cm (1 ft): Level 3
Radiated Radio Frequency: IEC 60255-22-3 1989
ENV 50140 1993 10 V/m
ENV 50204 1995 10 V/m (900 MHz with modulation)
IEEE C37.90.2 1995 10 V/m
10BASE-FL: Level 3 at –27 dBm
100BASE-FX: Level 3
10/100BASE-T with STP cable: Level 3
Fast Transient Disturbance: IEC 60255-22-4 1992
IEC 61000-4-4 1995 Level 4
Note: Some ESD tests may result in an interruption of communications. Operation of the host will
not be disrupted. The host and SEL-2701 are not damaged under the test conditions.
Certifications
ISO: Designed and manufactured using ISO-9001 certified quality program.