3.7
Date Code 20020501 SEL-2701 Ethernet Processor Instruction Manual
Settings and Commands
Data Access Settings
To determine which modes are available in your installation, see the host-
specific section. The SEL-2701 acts as a Telnet server for connections to the
SEL-2701 user interface. The user interface provides access to commands for
diagnostics and other special features of the SEL-2701. Telnet settings are
listed in Table 3.6.
UCA2 for
Field Devices
The SEL-2701 acts as a UCA2 interface for the host. The UCA2 interface
consists of several components that make up the UCA2 for Field Devices
standard. The SEL-2701 supports Generic Object Model for Substation and
Feeder Equipment (GOMSFE) and Generic Object Oriented Substation Event
(GOOSE).
UCA2 Settings
Table 3.7 on page 3.8 lists UCA2 settings. See the host-specific sections to
access UCA2 settings.
Tabl e 3.6 SEL - 2701 Te ln e t Sett i ng s
Label Description Range Default
T1CBAN Host Telnet connect banner 254 characters HOST
TERMINAL SERVER:
T1INIT Telnet session from host
enable
Y, N Y
T1RECV Telnet session to host enable Y, N N
T1PNUM
a
a
If you change these settings and accept the new settings, the SEL-2701 closes all active
network connections and briefly pauses network operation.
Host Telnet TCP/IP port 1–65534
except 20, 21, 102
23
T2CBAN SEL-2701 Telnet connect
banner
254 characters SEL-2701
TERMINAL SERVER:
T2RECV Telnet session to SEL-2701
enable
Y, N N
T2PNUM
a
SEL-2701 Telnet TCP/IP
port
1–65534
except 20, 21, 102
1024
TIDLE Telnet connection timeout
(0 prevents timeout)
0–255 minutes 5