B.8
SEL-2701 Ethernet Processor Instruction Manual Date Code 20020501
UCA2 GOMSFE Models
SEL Relay Virtual Device
FltMagA3 Magnitude of fault currents o
PhsAf r A-phase fault current o HISTORY:IA3
PhsBf r B-phase fault current o HISTORY:IB3
PhsCf r C-phase fault current o HISTORY:IC3
Neutf r Neutral fault current o HISTORY:IN3
q r Quality of data o #21
FltMagA4 Magnitude of fault currents o
PhsAf r A-phase fault current o HISTORY:IA4
PhsBf r B-phase fault current o HISTORY:IB4
PhsCf r C-phase fault current o HISTORY:IC4
Neutf r Neutral fault current o HISTORY:IN4
q r Quality of data o #21
FltMag Magnitude of fault current o
fr oHISTORY:CURR
q r Quality of data o #21
FltLoc Location of fault o
fr oHISTORY:LOC
HISTORY:FAULT_LOC
q r Quality of data o #21
FltTim r Time and date of fault o HISTORY:MONTH #30
FltDur r Fault duration in cycles o HISTORY:DURR
FltFrq r Frequency at fault o HISTORY:FREQ
ST
FltTar r Relay targets at time of
fault
o HISTORY:TARGET
HISTORY:TARGETS #31
FltTyp r Fault type for common
fault types
oHISTORY:TYPE
HISTORY:EVENT #32
FltTyp2 r Other fault types o HISTORY:TYPE
HISTORY:EVENT #33
FltSht r Shot counter at fault o HISTORY:SHOT
FltSG r Settings group number at
fault
oHISTORY:GROUP
Table B.9 Generic Control Model (GCTL)—SEL Relay Connected to an SEL-2030
FC Name r/w Description m/o Decode Method
ST
OD1–OD16 State last written to this control
point
m RB1–RB16
b2 r Status of bit m #19
CO
OD1–OD16 Control bit m RB1–RB16
OperDev rw
Control bit (01 to clear; 10 to set)
m
#20
Table B.8 Fault Identification Model (FAULT)—
SEL Relay Connected to an SEL-2030 (Sheet 2 of 2)
FC Name r/w Description m/o Decode Method