Date Code 20181001 SEL-3031 Instruction Manual
Appendix A
U.Instru ction M anua l
Firmware and Manual Versions
Firmware
Determining the Firmware Version in Your Device
To determine the firmware version, view the status report by using the serial port
STATUS command. The status report displays the Firmware Identification (FID)
number.
The firmware version number is after the R, and the release date is after the D. For
example, the following string shows firmware version number 100 with a release date
of October 9, 2009:
FID=SEL-3031-R100-V0-Z001001-D20091009
Table A.1 lists the firmware versions, revision descriptions, and corresponding
instruction manual date codes.
Table A.1 Firmware Revision History (Sheet 1 of 2)
Firmware Identification
(FID) Number
Summary of Revisions
Manual
Date Code
SEL-3031 Firmware Version:
SEL-3031-R104-V0-Z003001-
D20111228
FPGA Version:
SEL-3031-R101-D20101018
SEL-3044 Firmware Version:
SEL-3044-R102-V0-Z001001-
D20111223
Note: The SEL-3044
Encryption Card can only be
upgraded by sending the card
back to the factory. Please
contact the factory for assis-
tance.
➤ Fixed an issue in the SEL-3044 where
the random number generator seed
issued matching back-to-back samples
that caused the card to stop passing data.
➤ Fixed an issue in the SEL-3044 where
time-out behavior is treated as a hard
failure causing the card to stop communi-
cating.
➤ Corrected a key-handling issue in the
SEL-3044 forcing the master to set the
sequence key to 0 every time the slave
requests a new key.
20111228